| поискавой системы для электроныых деталей |
|
ADE9078ACPZ датащи(PDF) 42 Page - Analog Devices |
|
|
|||||||||||||||||||||||||||||
ADE9078ACPZ датащи(HTML) 42 Page - Analog Devices |
|
42 / 108 page ![]() Data Sheet ADE9078 Rev. 0 | Page 41 of 107 If VARACC = 0, the total and fundamental reactive energy accumulation is signed. The MSB of the AVARHR_HI register indicates whether the energy is negative or positive. Other accumulation modes offered include positive only accumulation mode with VARACC = 10, and negative only accumulation mode where only negative reactive energy is accumulated with VARACC = 11. No Load Detection No load detection prevents energy accumulation due to noise, when the input currents are below a given meter start current. To determine if a no load condition is present, the ADE9078 evaluates if the accumulated energy is below a user defined threshold over a user defined time period. This no load detection is done on a per phase and per energy basis. The NOLOAD_TMR bits in the EP_CFG register determine whether to evaluate the no load condition over 64 samples to 4096 samples (64/4 kSPS = 16 ms to 1.024 sec) by writing to the NOLOAD_TMR bits as described in Table 19. No load detection is enabled by default, over the minimum time of 64/4 kSPS = 16 ms. No load detection is disabled when the NOLOAD_TMR[2:0] bits in the EP_CFG register = 111b. Table 19. No Load Condition Evaluation Time NOLOAD_TMR Samples to Evaluate in No Load Condition TimeThat No Load Detection Is Evaluated (ms) 0 64 16 1 128 32 2 256 64 3 512 128 4 1024 256 5 2048 512 6 4096 1024 7 No load disabled No load disabled The user defined no load thresholds are written into the ACT_NL_LVL, REACT_NL_LVL, and APP_NL_LVL registers. The ACT_NL_LVL register sets the no load threshold for the total active energy. Correspondingly the REACT_NL_LVL register sets the no load threshold for total and fundamental reactive energy whereas the APP_NL_LVL sets the no load threshold for total apparent energy. The no load thresholds are calculated according to the following equation: × = X SCALE FULL xWATT LVL xNL 64 _ _ _ where: xWATT_FULL_SCALE is the nominal xWATT value with full- scale inputs, 20,823,646. Note that xVAR and VA have the same scaling so the same value can be used for all three thresholds. X is the desired no load input power level. For example, to set the no load threshold to zero out energy below 50,000 from full scale, X = 50,000. Thus, for a 50,000:1 no load threshold level, xNL_LVL is 0x6804. E 1 68 x 0 654 , 26 000 , 50 64 20,823,646 _ = = × = LVL xNL When a phase is in no load, every fDSP = 4 kSPS, zero energy is accumulated into the energy registers and CF accumulation. Note that the x_ACC registers are not affected by no load detection. Even when in no load, any power calculated in the respective xWATT, xVAR, and xVA registers is accumulated into the corresponding x_ACC register every fDSP = 4 kSPS. No Load Indications The PHNOLOAD register indicates whether each phase of energy is in no load. For example, Bit 2 through Bit 0 in the PHNOLOAD register indicate whether Phase A total apparent energy, reactive energy, and active energy are in phase on Bit 2 through Bit 0, respectively. If a bit is set, it indicates that the phase energy is in no load—if it is clear, the phase is not in no load. The user can enable an interrupt to occur when the no load status of one of the per phase energy changes, either going into or out of no load. There is an interrupt enable bit for each type of energy. Set the RFNOLOAD, VANLOAD, RNLOAD, and ANLOAD bits in the STATUS1 register to enable an interrupt on IRQ1 when one or more phases of fundamental VAR, total VA, total VAR, and total active power no load changes status. There is also an option to indicate the no load status on the EVENT pin (see the Interrupts/Events section for more information). Figure 62 shows what happens when the xWATT, low-pass filtered active power value goes above the user configured, no load threshold and then back down below it again. The same concept applies to all of the energy values (total and fundamental VAR, total VA) with the corresponding REACT_NL_LVL and APP_NL_LVL no load thresholds. LOW-PASS FILTERED ACTIVE POWER (xWATT) ACTIVE ENERGY NO LOAD THRESHOLD (ACT_NL_LVL) NO LOAD ACCUMULATION INTERVAL IS SET IN NOLOAD_TMR ACTIVE ENERGY NO LOAD ACCUMULATOR NO LOAD INDICATION ANOLOAD) ACTIVE ENERGY, xWATTHR Figure 62. No Load Detection and Indication |
|
ссылки URL |
| Вашему бизинису помогли Аллдатащит? [ DONATE ] |
Что такое Аллдатащит | реклама | контакт | Конфиденциальность | Ссылка на техническое описание | обмен ссыками | поиск по производителю All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |