поискавой системы для электроныых деталей
  Russian  ▼
ALLDATASHEETRU.COM

X  

CP5.241-S2 датащи(PDF) 7 Page - PULS GmbH

номер детали CP5.241-S2
подробное описание детали  24V, 5A, 120W, SINGLE PHASE INPUT
PDF  28 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
производитель  PULS [PULS GmbH]
домашняя страница  http://www.pulspower.com/
Logo PULS - PULS GmbH

CP5.241-S2 датащи(HTML) 7 Page - PULS GmbH

Back Button CP5.241-S2 Datasheet HTML 3Page - PULS GmbH CP5.241-S2 Datasheet HTML 4Page - PULS GmbH CP5.241-S2 Datasheet HTML 5Page - PULS GmbH CP5.241-S2 Datasheet HTML 6Page - PULS GmbH CP5.241-S2 Datasheet HTML 7Page - PULS GmbH CP5.241-S2 Datasheet HTML 8Page - PULS GmbH CP5.241-S2 Datasheet HTML 9Page - PULS GmbH CP5.241-S2 Datasheet HTML 10Page - PULS GmbH CP5.241-S2 Datasheet HTML 11Page - PULS GmbH Next Button
Zoom Inzoom in Zoom Outzoom out
 7 / 28 page
background image
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series
24V, 5A, 120W, SINGLE PHASE INPUT
Feb. 2018 / Rev. 0.3 DS-CP5.241-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
7/28
P R E L I M I N A R Y
6. OUTPUT
The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage.
The output is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large
capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance > 0.4F are connected to
the output, the unit might charge the capacitor in the HiccupPLUS mode.
Output voltage
Nom.
24V
Adjustment range
Min.
24-28V
Guaranteed value
Max.
30.0V
This is the maximum output voltage which can occur
at the clockwise end position of the potentiometer
due to tolerances. It is not a guaranteed value which
can be achieved.
Factory settings
Typ.
24.1V
±0.2%, at full load and cold unit
Line regulation
Max.
10mV
Between 85 and 300Vac
Load regulation
Max.
50mV
Between 0A and 6A, static value, see Fig. 6-1
Ripple and noise voltage
Max.
50mVpp
Load >0.2A, Bandwidth 20Hz to 20MHz, 50Ohm
Max.
200mVpp
Load <0.2A, Bandwidth 20Hz to 20MHz, 50Ohm
Output current
Nom.
6A1)
At 24V and an ambient temperatures below 45°C
Nom.
5A
At 24V and 60°C ambient temperature
Nom.
3.8A
At 24V and 70°C ambient temperature
Nom.
5.1A1)
At 28V and an ambient temperatures below 45°C
Nom.
4.3A
At 28V and 60°C ambient temperature
Nom.
3.2A
At 28V and 70°C ambient temperature
Fuse breaking current
Typ.
15A
Up to 12ms once every five seconds, see Fig. 6-2.
The fuse braking current is an enhanced transient current which helps to
start heavy loads or to trip fuses on faulty output branches. The output
voltage stays above 20V. See chapter 23.1 for additional measurements.
Overload protection
Included
Electronically protected against no-load, overload and
short circuit. In case of a protection event, audible
noise may occur.
Overload behaviour
Continuous current
Output voltage > 13Vdc, see Fig. 6-1
HiccupPLUS mode 2)
Output voltage < 13Vdc, see Fig. 6-1
Overload/ short-circuit current
Max.
7.5A
Continuous current, see Fig. 6-1
Typ.
9A
Intermitted current peak value for typ. 1s
Load impedance 50mOhm, see Fig. 6-3
Discharge current of output capacitors is not
included.
Max.
3.5A
Intermitted current average value (R.M.S.)
Load impedance 50mOhm, see Fig. 6-3
Output capacitance
Typ.
2 000μF
Included inside the power supply
Back-feeding loads
Max.
35V
The unit is resistant and does not show malfunctioning when a load feeds
back voltage to the power supply. It does not matter whether the power
supply is on or off. The absorbing energy can be calculated according to
the built-in large sized output capacitor.
1) This current is also available for temperatures up to +70°C with a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
2) HiccupPLUS Mode:
At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 1s. After this, the
output is switched off for approx. 9s before a new start attempt is automatically performed. This cycle is repeated as long as the overload
exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3.



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28


датащи скачать

Go To PDF Page


ссылки URL



Вашему бизинису помогли Аллдатащит?  [ DONATE ] 

Что такое Аллдатащит   |   реклама   |   контакт   |   Конфиденциальность   |   Ссылка на техническое описание    |   обмен ссыками   |   поиск по производителю
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com