Back Button PM5310 Datasheet HTML 4Page - Schneider Electric PM5310 Datasheet HTML 5Page - Schneider Electric PM5310 Datasheet HTML 6Page - Schneider Electric PM5310 Datasheet HTML 7Page - Schneider Electric PM5310 Datasheet HTML 8Page - Schneider Electric PM5310 Datasheet HTML 9Page - Schneider Electric PM5310 Datasheet HTML 10Page - Schneider Electric PM5310 Datasheet HTML 11Page - Schneider Electric PM5310 Datasheet HTML 12Page - Schneider Electric Next Button
Zoom Inzoom in Zoom Outzoom out
 8 / 14 page
background image
PM5000 technical specifications
PM5100
PM5300
PM5500
PM5600
PM5700
Inputs / Outputs / Mechanical Relays
Digital inputs
2
4 in PM5560, PM5561, PM5562, PM5563, PM5580, PM5650
2 in PM5570, PM5660, PM5661, PM5760, PM5761
Digital outputs
1 (kWh only)
2
2 (Solid state)
Form A Relay outputs
2
Analog inputs
2 for PM5570
Residual Current inputs
2 for PM5660
2 for PM5760
Timestamp resolution in seconds
1
1
1
1
1
Whetting source
24 V DC, 8 mA
Type of measurement: True rms on
three-phase (3P, 3P + N)
64 samples per cycle
128 samples per cycle
Measurement
accuracy
IEC 61557-12
PMD/[SD|SS]/K70/0.5
PMD/[SD|SS]/K70/0.2
Active Energy
Class 0.5S as per IEC 62053-22/ Class 0.5 as
per IEC 61557-12/ ± 0.5%
Class 0.2S as per IEC 62053-22/ Class 0.2 as per IEC 61557-12/
± 0.2%
Reactive Energy
Class 2 as per IEC 62053-23/ Class 1.0 as
per IEC 61557-12/ ± 1.0%
Class 2 as per IEC 62053-23/ Class 1.0 as per IEC 61557-12/
± 1.0%
Active Power
Class 0.5 as per IEC 61557-12/ ± 0.5%
Class 0.2 as per IEC 61557-12/ ± 0.2%
Apparent Power
Class 0.5 as per IEC 61557-12/ ± 0.5%
Class 0.5 as per IEC 61557-12/ ± 0.5%
Reactive Power
Class 1.0 as per IEC 61557-12/ ± 1.0%
Class 1.0 as per IEC 61557-12/ ± 1.0%
Current, Phase
Class 0.5 as per IEC 61557-12/ ±0.5 %
Class 0.2 as per IEC 61557-12/ ±0.15 %
Voltage, L-N
Class 0.5 as per IEC 61557-12/ ± 0.5 %
Class 0.2 as per IEC 61557-12/ ± 0.1 %
Frequency
Class 0.05 as per IEC 61557-12/ ±0.05 %
Class 0.05 as per IEC 61557-12/ ±0.05 %
Power Factor
Class 0.5 as per IEC 61557-12/ ±0.005 count
Class 0.5 as per IEC 61557-12/ ±0.005 count
Voltage unbalance
Class 5/ ±5%
Class 2/ ±2%
Voltage harmonics
Class 5/ ±5%
Class 2/ ±2%
Voltage THD Class
Class 5/ ±5%
Class 2/ ±2%
Current harmonics
Class 5/ ±5%
Class 2/ ±2%
Current THD Class
Class 5/ ±5%
Class 2/ ±2%
MID Directive
EN50470-1,
EN50470-3
Annex B and Annex D (Optional model references) Class C
Input-voltage
(up to 1.0
MV AC max,
with voltage
transformer)
Nominal Measured
Voltage range
20 V L-N / 35 V L-L to 400 V L-N /690 V L-L
absolute range 35 V L-L to 760 V L-L
20 V L-N / 20 V L-L to 400 V L-N /690 V L-L
absolute range 20 V L-L to 828 V L-L
Impedance
5 MΩ
Frequency nominal
50 or 60 Hz ±5 %
50 or 60 Hz ±10 %
Input-current
(configurable
for 1 or 5 A
secondary
CTs)
I nominal
5 A
Measured Amps with
over range
Starting current: 5 mA
Operating range: 50 mA to 8.5 A
Starting current: 5 mA
Operating range: 50 mA to 10 A (with Crest Factor)
Withstand
Continuous 20 A, 10 s/hr 50 A, 1 s/hr 500 A
Impedance
< 0.3 mΩ
Frequency nominal
50 or 60 Hz ±5 %
50 or 60 Hz ±10 %
Burden
<0.026 VA at 8.5 A
AC control
power
Operating range
100 - 277 V AC L-N / 415 V L-L +/-10 %
CAT III 300V class per IEC 61010
100-480 V AC ±10 %
CAT III 600V class per IEC 61010
Burden
<5 W,11 VA at 415V L-L
<5W/16.0 VA at 480 V AC
Frequency
45 to 65 Hz
Ride through time at
maximum burden
80 mS typical at 120V AC
100 mS typical at 230 V AC
100 mS typical at 415 V AC
35 ms typical at 120 V L-N
129 ms typical at 230 V L-N
DC control
power
Operating range
125–250 V DC ±20 % (100 to 300 V DC)
Burden
<4 W at 250 V DC
typical 3.1 W at 125 V DC, max. 5 W
Ride-through time
50 mS typical at 125 V DC and maximum burden
LV DC control
power
20-60 V DC ±10 %
CAT III
Burden 4.1 W max.
b PM5580
PM5000 series
BASIC MULTI-FUNCTION METERING
FUNCTIONS AND CHARACTERISTICS
Version: 1.0 - 04/02/2023
PLSED310052EN
8



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14


датащи скачать

Go To PDF Page


ссылки URL



Вашему бизинису помогли Аллдатащит?  [ DONATE ] 

Что такое Аллдатащит   |   реклама   |   контакт   |   Конфиденциальность   |   Ссылка на техническое описание    |   обмен ссыками   |   поиск по производителю
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com