20 / 26 page ![]() 3-phase systems AN3157 20/26 Doc ID 17105 Rev 1 In the balanced loads, the sum of the two wattmeter readings gives the total power. This can be proven in a star-connected load mathematically using the power reading of each meter as: Equation 10 Equation 11 Equation 12 The difference between the readings is computed as follows: Equation 13 which is 1/ √3 times the total 3-phase reactive power (see Equation 8). This means that the two-wattmeter method can also indicate the total reactive power in the 3-phase loads and also the power factor. Figure 14. The two-wattmeter method in star- or delta-connected load. () ) 30 cos( I V 30 cos I V P line line 1 12 1 θ + ° = θ + ° = () ) 30 cos( I V 30 cos I V P line line 3 32 2 θ − ° = θ − ° = θ = + = cos I V 3 P P P line line 2 1 Total θ = θ + ° − θ − ° = − sin I V ) 30 cos( I V ) 30 cos( I V P P line line line line line line 1 2 |
|
|
ссылки URL |
| Вашему бизинису помогли Аллдатащит? [ DONATE ] |
Что такое Аллдатащит | реклама | контакт | Конфиденциальность | Ссылка на техническое описание | обмен ссыками | поиск по производителю All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|