Back Button 3G5A2-RPT01-E Datasheet HTML 101Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 102Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 103Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 104Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 105Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 106Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 107Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 108Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 109Page - Omron Electronics LLC Next Button
Zoom Inzoom in Zoom Outzoom out
 105 / 182 page
background image
92
5-3
Error Processing and Correction
CPU Rack/Expansion CPU Rack/Expansion I/O Rack
Symptom
Cause
Remedy
POWER indicator is unlit.
PCB short-circuited or damaged by heat.
Replace Power Supply Unit or Backplane.
RUN indicator is unlit.
(1) START input terminals are OFF.
Short-circuit START input terminals.
(2) Error in program.
Correct program
(3) Power line is faulty.
Replace Power Supply Unit.
RUN output does not
turn ON.
RUN indicator lit.
Internal circuitry of
Power Supply Unit is faulty.
Replace Power Supply Unit.
Link Unit or CPU Bus Unit
dlf
(1) CPU cable is faulty.
Replace CPU cable.
does not operate or malfunc-
tions
(2) CPU bus is faulty.
Replace Backplane.
tions.
(3) Expansion CPU Rack is faulty.
Replace I/O Control or I/O Interface Unit.
Bit does not operate.
I/O bus faulty.
Replace Backplane.
Error occurs in units of 8
i
(1) I/O cable is faulty.
Replace I/O cable.
points.
(2) I/O bus is faulty.
Replace Backplane.
(3) Expansion I/O Rack is faulty.
Replace I/O Control or I/O Interface Unit.
I/O bit turns ON
I/O bus is faulty.
Replace Backplane.
All bits for one Unit do not
turn ON.
I/O bus is faulty.
Replace Backplane.
Error Processing and Correction
Section 5-3



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100  ...More


датащи скачать

Go To PDF Page


ссылки URL



Вашему бизинису помогли Аллдатащит?  [ DONATE ] 

Что такое Аллдатащит   |   реклама   |   контакт   |   Конфиденциальность   |   Ссылка на техническое описание    |   обмен ссыками   |   поиск по производителю
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com