TEMPERATURE-SPAN DISTANCE APPLICATION
INFORMATION
Cable-pull switches featuring broken cable detection require
pre-tensioning in order to enable the RUN condition.
The relative expansion or contraction of the steel actuating
cable when the ambient temperature increases or decreases
must be taken into account when pre-tensioning a cable pull
switch.
The change in cable length with change in temperature can
cause significant nuisance shut downs on longer runs.
Install the system when the temperature is at the mid point of
the extremes. If a warehouse has a low temperature of 15.6 °C
[60 °F]and a high of 32.2 °C [90 °F], set up the system at the
midpoint 23.9 °C [75 °F].
Use an endspring or another CPS at the opposite end of the
cable span to double the temperature tolerance and to meet
the requirements of EN 418.
Figure 3. Total Temperature Variation vs. Cable Span