Back Button BUS Datasheet HTML 29Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 30Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 31Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 32Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 33Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 34Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 35Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 36Page - Christian Bürkert GmbH & Co. KG BUS Datasheet HTML 37Page - Christian Bürkert GmbH & Co. KG Next Button
Zoom Inzoom in Zoom Outzoom out
 33 / 42 page
background image
Type büS
Best practice instructions
33
12.9
Power consumption
It is important to consider the power consumption of a device as early as possible in the planning. Using
the information about the total power consumption of the network, the accessories and the number of
power supplies can be planned.
Furthermore, the permitted voltage ripple of a device must be considered. For devices with direct access,
e.g. MFCs, it is important to have a low residual ripple. For sensors, the impact is not that significant.
12.10
Grounding power supplies
Power supplies should not be earthed, but it is important to ensure galvanic isolation. Otherwise, huge
loops may develop that can have a negative impact on the entire network.
12.11
Shielding of büS network
Provide good, continuous functional earth (FE) with low impedance and noise. If this cannot be ensured in
the area of the büS network, use a low-impedance metallic cable duct or bypass conductor grounded on
both sides to prevent compensation currents over büS shield.
Connect devices of the internal shielding "None" directly to the büS strand (without stitch). The shielding
must be on upstream or downstream devices in the network, but at least on end devices.
Connect at least one point of büS shield directly to FE (e.g. by using a device with direct FE connection to
shield).
Keep a distance from H-Field emitting machines with high power consumption. If not possible, use metal
duct grounded on both sides or multiple times for additional shielding of the büS cable .



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42


датащи скачать

Go To PDF Page


ссылки URL



Вашему бизинису помогли Аллдатащит?  [ DONATE ] 

Что такое Аллдатащит   |   реклама   |   контакт   |   Конфиденциальность   |   Ссылка на техническое описание    |   обмен ссыками   |   поиск по производителю
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com