M2VS-162-R
AI

The **M2VS-162-R** is a specific model within the **M2VS Series** of ultra-slim signal conditioners (transmitters) manufactured by **M-System**. These devices are used in industrial automation to convert one type of electrical signal into another, providing isolation and signal normalization.
---
### 1. Part Number Breakdown
To understand the electronic capabilities, we must decode the suffix codes:
| Code Segment | Description | Specific Detail |
| :--- | :--- | :--- |
| **M2VS** | Base Series | Ultra-slim Signal Conditioner |
| **1** | Input Type | **DC Voltage** (Selectable ranges) |
| **6** | Output Type | **1 – 5V DC** |
| **2** | Power Supply | **24V DC** |
| **R** | Special Feature | **RoHS Compliant** / Standard Options |
---
### 2. Key Electronic Specifications
The M2VS-162-R is designed for high-density mounting and precise signal processing.
#### A. Input and Output
* **Input (Code 1):** Typically handles DC voltages ranging from ±10mV to ±1000V depending on internal settings (commonly set for 0-10V or 0-5V).
* **Output (Code 6):** Fixed at **1 to 5V DC** with a load resistance requirement of $\ge 2500 \Omega$.
* **Response Time:** $\le 0.5$ seconds (0 – 90%).
#### B. Isolation and Power
* **Isolation:** 3-way isolation (Input to Output to Power).
* **Dielectric Strength:** 2000V AC @ 1 minute.
* **Power Input:** 24V DC ($\pm 10\%$), ripple 10% p-p max.
* **Current Consumption:** Approx. 30 mA.
#### C. Physical Design
* **Construction:** Slim-line housing (approx. 5.9 mm wide).
* **Mounting:** DIN rail mounting.
* **Connection:** Tension-clamp (spring) or screw terminals depending on the exact sub-variant.
---
### 3. Internal Component Functions
The electronic architecture generally consists of three main stages:
1. **Input Conditioning:** An operational amplifier circuit scales the incoming DC voltage and protects the internal circuitry from spikes.
2. **Isolation Barrier:** Uses an optoisolator or a transformer-coupled isolator to prevent ground loops and protect control systems (like PLCs) from high-voltage surges on the field side.
3. **Output Driver:** Converts the isolated signal into a stable **1-5V DC** signal, ensuring low noise and high linearity.
---
### 4. Application Use Case
This part is typically used in environments where space is limited on a DIN rail.
* **Example:** Converting a 0-10V sensor signal into a 1-5V signal for a legacy PLC input module while ensuring the two systems are electrically isolated to prevent interference.
- ⤷
What are the wiring pin assignments for the M2VS-162-R?
- ⤷ Can this module be used for current inputs like 4-20mA?
- ⤷ What is the operating temperature range for this signal conditioner?