KAC-ACD-R
AI

The **KAC-ACD-R** is an addressable manual call point (MCP) designed specifically for fire alarm systems using the **System Sensor/Notifier** protocol. It is an electronic component that allows building occupants to manually trigger a fire alarm by pressing or breaking a front element.
---
### 1. Key Electronic Components & Specifications
The KAC-ACD-R is more than just a mechanical switch; it contains integrated circuitry to communicate with a Fire Alarm Control Panel (FACP).
| Component | Technical Detail |
| :--- | :--- |
| **Communication Protocol** | Advanced/Analogue Addressable (System Sensor) |
| **Operating Voltage** | 15V to 32V DC (Powered by the SLC Loop) |
| **Current Consumption** | ~200μA (Standby) / ~7mA (Alarm - LED on) |
| **Addressing** | Rotary Switches (01-159) or Digital Addressing |
| **Indicator** | Tri-color LED (Red for Alarm, Green for Polling) |
| **Termination** | Plug-and-play terminal blocks (up to 2.5mm² wire) |
---
### 2. Functional Electronic Features
#### A. Rotary Address Switches
Unlike conventional switches, the KAC-ACD-R features two rotary dials on the back of the electronic module. These are used to set a unique decimal address (e.g., 01, 15, 99). This allows the control panel to identify exactly which device has been activated.
#### B. Integrated Logic Circuitry
The internal PCB (Printed Circuit Board) handles:
* **Polling:** Responding to the control panel's status requests.
* **Interrupt Function:** When activated, the device sends an immediate "interrupt" signal to the panel, ensuring a response time of less than 3 seconds.
* **Built-in Isolator (Optional):** Some versions include a short-circuit isolator to protect the rest of the loop if a cable fault occurs.
#### C. LED Status Signaling
The electronics drive a high-visibility LED:
* **Blinking Green:** Normal operation (polling).
* **Steady Red:** Alarm condition.
* **Yellow/Amber:** Fault or isolation (on specific models).
---
### 3. Connection Diagram Overview
The electronic interface uses a simple two-wire connection to the Signaling Line Circuit (SLC):
```text
[Loop In +] ---- (1)
[Loop In -] ---- (2) Internal Circuitry --- [Rotary Switches]
[Loop Out +] ---- (3) |
[Loop Out -] ---- (4) [Bi-color LED]
```
---
### 4. Environmental & Physical Characteristics
* **IP Rating:** Typically IP24D (Indoor use).
* **Material:** Flame retardant ABS plastic.
* **Plug-and-Play:** The "E-Z Fit" connector allows the backbox to be wired independently of the electronic front element, preventing damage to the PCB during construction.
---
- ⤷
How do you set the rotary address switches on the KAC-ACD-R?
- ⤷ What is the difference between the ACD and the MCP models?
- ⤷ Can this call point be used on a conventional 24V fire system?