FLM-2E-R
AI

The **FLM-2E-R** is a specialized electronic component primarily used in fire alarm systems and industrial control panels. It is commonly identified as a **Relay Module** (Form C) within the Bosch Fire Alarm peripheral line.
Below is a detailed breakdown of its electronic specifications and functions.
---
### 1. Technical Specifications
The FLM-2E-R is an addressable module that connects to a Local Security Network (LSN) and provides a physical relay output for controlling external devices.
| Feature | Specification |
| :--- | :--- |
| **Input Voltage** | 15 V DC to 33 V DC (via LSN) |
| **Current Consumption** | Max 1.0 mA (standby/active) |
| **Relay Contact Rating** | 1 A at 30 V DC / 0.5 A at 42.4 V AC |
| **Relay Type** | Form C (Change-over contact) |
| **Address Range** | 0 to 254 (Set via rotary switches) |
| **Protection Class** | IP 30 |
---
### 2. Key Electronic Components
The internal circuitry of the FLM-2E-R consists of several critical stages:
* **LSN Bus Transceiver:** This sub-circuit handles the data communication between the fire panel and the module. It interprets digital signals to trigger the relay.
* **Microcontroller:** A low-power IC that manages the module's unique address and executes logic commands (e.g., "Switch Relay On").
* **Bistable Relay:** The "heart" of the device. It uses an electromagnetic coil to switch between the **Common (C)**, **Normally Open (NO)**, and **Normally Closed (NC)** contacts.
* **Rotary Switches:** Three physical dials on the board used to set the decimal address of the module on the loop.
* **LED Indicator:** A surface-mount LED that flashes to indicate communication or a steady red light to indicate an active relay state.
---
### 3. Wiring Diagram (Terminal Overview)
The module features screw terminals for easy integration. The following table describes the standard pinout:
| Terminal | Label | Description |
| :--- | :--- | :--- |
| **1 & 2** | LSN a1/b1 | Incoming LSN bus connection |
| **3 & 4** | LSN a2/b2 | Outgoing LSN bus (to next device) |
| **5** | NC | Normally Closed contact |
| **6** | C | Common contact |
| **7** | NO | Normally Open contact |
---
### 4. Operational Logic
The FLM-2E-R operates as a **dry contact**. This means it does not provide voltage to the external device; it simply acts as a switch.
1. **Input:** Receives a digital signal from the Fire Alarm Control Panel (FACP) via the LSN bus.
2. **Processing:** The onboard IC verifies the address.
3. **Output:** The relay coil is energized, moving the contact from NC to NO. This is typically used to shut down HVAC fans, release door magnets, or trigger elevators.
- ⤷
What is the maximum distance allowed for the LSN bus connection to this module?
- ⤷ Can the FLM-2E-R be used to switch high-voltage 220V AC loads directly?
- ⤷ How do you reset the relay state after a fire alarm event?