The **8536SDO2V02S** is a specific model of a NEMA-rated magnetic motor starter manufactured by **Square D (Schneider Electric)**. It is part of the Type S product line, designed for starting and stopping AC motors while providing thermal overload protection.
---
### Technical Specifications Breakdown
The following table outlines the core electronic and mechanical characteristics of this specific unit:
| Parameter | Specification Details |
| :--- | :--- |
| **Manufacturer** | Square D (Schneider Electric) |
| **NEMA Size** | Size 2 |
| **Continuous Ampere Rating** | 45 Amperes |
| **Poles** | 3-Pole (3-Phase operation) |
| **Control Voltage (Coil)** | 110V AC @ 50Hz / 120V AC @ 60Hz |
| **Enclosure Type** | Open (No metal box/NEMA 1 cabinet) |
| **Overload Type** | Melting Alloy (requires separate thermal units) |
| **Phase Support** | 3-Phase |
| **Motor Power (HP)** | 10 HP @ 200V / 15 HP @ 230V / 25 HP @ 460-575V |
---
### Key Electronic Components
#### 1. Magnetic Contactor
The heart of the device is the magnetic contactor. When the **120V AC coil (V02 suffix)** is energized, it creates an electromagnetic field that pulls the power contacts closed, allowing high-voltage electricity to flow to the motor.
#### 2. The Coil (V02 Code)
The "V02" in the part number specifically designates the coil voltage. This part is designed to interface with standard North American control circuits (120V).
- **Frequency:** Operates on both 50Hz and 60Hz.
- **Inrush/Sealed VA:** The coil draws higher current initially to close the contacts (Inrush) and then drops to a lower current to hold them closed (Sealed).
#### 3. Overload Relay Block
This unit features a "Melting Alloy" overload relay.
- **Thermal Units:** It requires the installation of "B-type" thermal heaters (sold separately) matched to the motor's Full Load Amps (FLA).
- **Protection:** If the motor draws too much current, the heat melts a low-temperature alloy in the heater, tripping a mechanical link that opens the control circuit and shuts down the motor.
#### 4. Auxiliary Contacts
The "S" suffix often denotes specific configurations or separate control features. Standard Type S starters usually include one normally open (N.O.) auxiliary contact, used for "holding" the circuit in place when a momentary "Start" button is used.
---
### Part Number Suffix Decoding
| Segment | Meaning |
| :--- | :--- |
| **8536** | Product Type (Non-reversing Motor Starter) |
| **S** | Series / Design Type (Type S) |
| **D** | NEMA Size (D = Size 2) |
| **O** | Enclosure Code (O = Open Style) |
| **2** | Number of Poles (3 Poles) |
| **V02** | Voltage Code (120V AC Coil) |
| **S** | Separate Control Circuit capability |
- ⤷
What are the compatible thermal heater units for a Size 2 Square D starter?
- ⤷ How do you wire a 3-wire start/stop station to the 8536SDO2V02S?
- ⤷ What is the difference between an Open (O) and NEMA 1 (G) enclosure for this model?